Data Centre Provisioning

The SRM forms that can be obtained here are required for the installation/configuration of racks and servers in the Data Centre. Please ensure that all forms are duly completed before submitting them to the NUSRT System which will be assessed by the DC Team thereafter.

For further clarifications or any related inquiries, kindly email us at CCDCEngr@nus.edu.sg

Please read the following documents before making your request:
Read Me First
SRM Commission Flowchart
SRM Decommission Flowchart

Maximum Floor Loading

Please ensure that the total equipment weight (inclusive of equipment and rack) does not exceed maximum allowable weight for DC floor loading as stated below, before submission of SRM to DC Team.

If the DC floor loading exceeds, requestor shall consult licensed structure engineer for advise and certification (if required) on how to spread the equipment load within the Data Centre floor area.

Data Centre Maximum Weight for Floor Loading
Max Weight (kg) = (Floor Loading in Newton / 9.81 ) * (Cabinet Footprint Area in meter² )
Note:
1 TLDC Floor Loading 10000 N/m²
2 HSDC Floor Loading 7500 N/m²
Maximum Rack Power and Cooling

Please ensure that the total equipment power and cooling does not exceed maximum allowable setting for DC as stated below, before submission of SRM to the DC Team.

Data Centre Maximum Rack Power and Cooling
Formula for Cooling is 1 watt = 3.412 BTU/Hour
Note:
1 TLDC Low Dense Rack Power and Cooling 3000W 10236 BTU/Hour
2 TLDC Mid Dense Rack Power and Cooling 8000W 27296 BTU/Hour
3 TLDC High Dense Rack Power and Cooling 15000W 51180 BTU/Hour
4 HSDC Rack Power and Cooling 6000W 20472 BTU/Hour
Various Forms

Below are the various forms that are required for submission to deliver/install/commission the equipment into the Data Centre and accessing or carry out work in Data Centre.